Features of fuses operating in medium voltage instrument transformers protection

User Rating:  / 0
PoorBest 

Authors:


O. M. Grechko*, orcid.org/0000-0001-7872-8585, National Technical University “Kharkiv Polytechnic Institute”, Kharkiv, Ukraine, e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.

Ye. I. Baida, orcid.org/0000-0003-0297-328X, National Technical University “Kharkiv Polytechnic Institute”, Kharkiv, Ukraine

Oleksandr H. Sereda, orcid.org/0009-0003-5243-3828, National Technical University “Kharkiv Polytechnic Institute”, Kharkiv, Ukraine

Olena H. Sereda, orcid.org/0000-0003-4658-9554, National Technical University “Kharkiv Polytechnic Institute”, Kharkiv, Ukraine

V. M. Buhaichuk, orcid.org/0000-0003-2236-1280, LLC “AVM AMPER”, Kremenchuk, Ukraine.

* Corresponding author e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.


повний текст / full article



Naukovyi Visnyk Natsionalnoho Hirnychoho Universytetu. 2026, (5): 092 - 100

https://doi.org/10.33271/nvngu/2026-5/092



Abstract:


The problem of protection of 6–35 kV voltage instrument transformers (VTs) of using fuses is associated with the lack of domestic manufacturers of fuses capable of effectively protecting VTs, especially when small overload currents flow.


Purpose.
Establishing the characteristics of fuse operating when protecting medium voltage instrument transformers 6–35 kV with cast insulation and determining the technical parameters of improved fuses that provide effective protection of instrument transformers when small overload currents flow.


Methodology.
Analytical and experimental methods were used to study the processes of fuse operating when protecting medium voltage instrument transformers. An analysis of the operating modes of 6–35 kV networks was carried out, the features of fuse operation at low overload currents were investigated, and laboratory experiments were performed to measure currents, voltages, and operating times. Based on the results obtained, criteria for selecting the parameters of improved fuses were formulated to increase the efficiency of transformer protection.


Findings.
The results of the conducted experimental studies and oscillograms from operating power facilities confirmed the problem of disconnecting small overload currents of VTs by fuses. It was experimentally established that when fuses protecting VTs switch off small overload currents, the fuse-link burns out, but the VT power circuit is not interrupted and voltage remains at the terminals of its secondary winding.


Originality.
Criteria for determining the parameters of fuses to increase the efficiency of VT protection are proposed and the feasibility of creating an improved fuse for VTs with a rated fuse-link current In 0.08–0.1 A, which ensures operating for 1 hour at a current I1h 0.15 А, is substantiated.


Practical value.
Ways of solving the problem of VT protection are proposed by improving the designs of fuses in order to improve their protective characteristics in the range of small overload currents.



Keywords:
fuse, fuse-link, medium voltage instrument transformer, instrument transformer protection, overvoltage, ferroresonance

References.


1. Zhurahivskyi, A. V., Kens, Y. A., Yatseyko, A. Y., & Maslyak, R. Y. (2013). Multi-protection system power grids 6–35 kV from ferroresonance processes. Technical Electrodynamics, (5), 70-76. http://previous.techned.org.ua/2013_5/st11.pdf

2. Zhurahivskyi, A. V., Kens, Y. A., Yatseyko, А. Y., & Maslyak, R. Y. (2010). Ferroresonance processes in electrical networks 10 kV with different voltage transformers. Technical Electrodynamics, (2), 73-78. http://previous.techned.org.ua/article/10-2/st9.pdf

3. Hanus, O., & Starkov, K. (2021). Study of the nature of overvoltages in the electrical network arising from voltage transformers. Bulletin of the National Technical University “KhPI”. Series: Energy: Reliability and Energy Efficiency, 1(2), 28-36. https://doi.org/10.20998/2224-0349.2021.01.05

4. Sayenko, Y. L., & Popov, A. S. (2011). Investigation of the damage cause of the voltage transformers using for insulation checking. Energy Saving. Power Engineering. Energy Audit, 7(89), 59-66. http://eee.khpi.edu.ua/article/view/21892

5. Malinovskyi, A. A., & Hushchyn, Ye. Yu. (2015). Network faults impact on operation of nom-10 voltage transformers. Naukovyi Visnyk Natsionalnoho Hirnychoho Universytetu, (1), 89-93.

6. Wang, K., Liu, H., Yang, Q., Yin, L., & Huang, J. (2019). Impact Transient Characteristics and Selection Method of Voltage Transformer Fuse. Energies, 12(4), 737. https://doi.org/10.3390/en12040737

7. Bajda, Y., Grechko, O., Buhaichuk, V., & Knápek, R. (2021). To the Problem of Protection of Medium Voltage Instrument Transformers with Fuses: Analytical Research. Lighting Engineering & Power Engineering, 60(3), 92-102. https://doi.org/10.33042/2079-424X.2021.60.3.02

8. Bajda, Y., & Grechko, O. (2023). Multiphysics calculation of fuses of medium voltage measuring transformers. Bulletin of NTU “KhPI”. Series: Problems of Electrical Machines and Apparatus Perfection. The Theory and Practice, 1(9), 3-10. https://doi.org/10.20998/2079-3944.2023.1.01

9. El-Shafhy, M. (2022). Ferroresonance in Distribution Systems – State of the Art. Przeglad Elektrotechniczny, 11, 3-17. https://doi.org/10.15199/48.2022.11.01

10.      Yang, M., Sima, W., Duan, P., Zou, M., Peng, D., Yang, Q., & Duan, Q. (2017). Electromagnetic transient study on flexible control processes of ferroresonance. International Journal of Electrical Power & Energy Systems, 93, 194-203. https://doi.org/10.1016/j.ijepes.2017.05.026

11.      McDermit, D. C., Shipp, D. D., Dionise, T. J., & Lorch, V. (2013). Medium-Voltage Switching Transient-Induced Potential Transformer Failures: Prediction, Measurement, and Practical Solutions. IEEE Transactions on Industry Applications, 49(4), 1726-1737. https://doi.org/10.1109/TIA.2013.2258453

12.      Pordanjani, I. R., Liang, X., Wang, Y., & Schneider, A. (2021). Single-Phase Ferroresonance in an Ungrounded System During System Energization. IEEE Transactions on Industry Applications, 57(4), 3530-3537. https://doi.org/10.1109/TIA.2021.3079878

13.      Saienko, Y. L., & Popov, A. S. (2010). Determination of the boundaries of existence of ferroresonance in the network with the insulated neutral and the electromagnetic voltage transformers VTOI-6-66 on the basis on the computer simulation. Energy Saving. Power Engineering. Energy Audit, 12(82), 9-16. https://eee.khpi.edu.ua/article/view/23019

14.      Saienko, Yu. L., & Popov, A. S. (2011). Simulation of ferroresonance phenomenon in distribution networks of metallurgical enterprises. Visnyk of Vinnytsia Politechnical Institute, (2), 91-95.
https://visnyk.vntu.edu.ua/index.php/visnyk/article/view/1400/1400

15.      ABB. Ferroresonance elimination VT Guard Pro (n.d.). https://new.abb.com/medium-voltage/apparatus/instrument-transformers-and-sensors-id/products/iec-indoor-voltage-transformers/ferroresonance-elimintation-vt-guard-pro

16.      Orion EE. Ferro-Damp. Ferroresonance Solutions (n.d.). https://orionee.com/products/ferroresonance-solution/ferro-damp

17.      Saienko, Yu. L., & Popov, A. S. (2012). Investigated ferroresonance processes without ground fault. Technical Electrodynamics, (6), 51-57. https://techned.org.ua/index.php/techned/article/view/1398/1280

18.      Tugay, Yu. I., Ganus, O. I., & Starkov, K. О. (2016). The switching in voltage transformer. Technical Electrodynamics, (5), 73-75. https://doi.org/10.15407/techned2016.05.073

19.      LLC “QUARTZ”. Current-limiting fuses of the PKT and PKN series. Technical description and operating instructions UICG.674351.004 (n.d.). https://quartz.zp.ua/uploads/files/products/pkt_pkn_ua.pdf

20.      LLC “Energozahyst”. High-voltage fuses of the PK(n) series (n.d.). https://energozahist.com.ua/catalog/high-voltage-fuses/p-511

21.      DSTU EN 60282-1:2016. High-voltage fuses. Part 1. Current-limiting fuses (EN 60282-1:2009, IDT). With corrections no. 1, 2016.

22.      International Electrotechnical Commission (2020). High-voltage fuses – Part 1: Current-limiting fuses (IEC Standard No. 60282-1:2020). (n.d.). https://webstore.iec.ch/publication/59817

23.      Grechko, O., & Kulyk, O. (2024). Current State and Future Prospects of Using SF6 Gas as an Insulation in the Electric Power Industry. 2024 IEEE 5 th KhPI Week on Advanced Technology (KhPIWeek), Kharkiv, Ukraine, 2024, (pp. 1-6). https://doi.org/10.1109/KhPIWeek61434.2024.10877987

24.      LZQJ-XC. 4-quadrant/combined meter (n.d.). https://emh-metering.com/en/products/special-meters/lzqj-xc

25.      Technical information for CheckMeter 2.3 genX (n.d.). https://www.mte.ch/products/checkmeter-23-genx-411/portable-test-equipment/checkmeter-23-genx-397

 

Guest Book

If you have questions, comments or suggestions, you can write them in our "Guest Book"

Registration data

ISSN (print) 2071-2227,
ISSN (online) 2223-2362.
Journal was registered by Ministry of Justice of Ukraine.
Registration number КВ No.17742-6592PR dated April 27, 2011.

Contacts

D.Yavornytskyi ave.,19, pavilion 3, room 24-а, Dnipro, 49005
Tel.: +38 (066) 379 72 44.
e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.
You are here: Home Home EngCat Archive 2026 Content №5 2026 Features of fuses operating in medium voltage instrument transformers protection